As a professional and high-quality manufacturer of Ceramic pillar high-voltage AC circuit breakers, you can rest assured to purchase Ceramic pillar high-voltage AC circuit breakers from our factory. We will provide you with the best after-sales service and timely delivery.
Ceramic pillar high-voltage AC circuit breaker is equipped with CT20 spring operating mechanism, adopts self-arc extinguishing principle, and has single-break structure. The three poles of each circuit breaker are installed on a frame to realize three-phase mechanical linkage through transmission mechanism. The electric control can realize remote and local operation.
Main technical parameters of the product
Item No. LW36-72.5
1 Rated voltage kV72.5
2 Rated current A 1250 3150
3 Rated short-circuit breaking current kA 31.5
4 Rated short-time withstand current kA31.5 (4s)
5 Rated peak withstand current kA 80
6 Rated lightning impulse withstand voltage kV break 350+60 to ground 350
7 Rated 1 min power frequency withstand voltage kV break 160+42 to ground 160
8 Mechanism model CT20 spring operating mechanism
Ceramic pillar high-voltage AC circuit breaker product performance features
1Excellent breaking performance
2Long electrical life
3Reliable insulation performance
4Long mechanical life
5Safe and reliable operation, low maintenance workload
Ceramic pillar high-voltage AC circuit breaker main technical parameters
Rated voltage
NAME
NUITV
LW36-72.5
LW25-126/145
LW25-252
LW15B-252/LW15-252
66
126/145
252
252
Rated frequency
Hz
50
50
50
50
Rated current
A
125,031,504,000
20,003,150
4000
31,504,000
Rated breaking current
kA
25,31.5
40/31.5
40
50
Rated closing current
kA
80
100/80
100
125
Rated short-time withstand current and duration
kA
31.5(4s)
40(4s)/31.5(4s)
40(4s)
50(4s)
Rated peak withstand current
kA
80
100/80
100
125
Near-zone fault breaking current
kA
lex 90%le x75%
Rated out-of-step breaking current
kA
lex 25%
Creepage distance
cm/kV
3.1
2.5,3.1
Break
kV
160+42
315
395+145
Dry Test
To ground
kV
160
275
460
1 minute power frequency withstand voltage
Between electrodes
kV
160
275
一一
-
1 minute power frequency withstand voltage
Break
kV
160+42
275
395+145
Wet test
To ground
kV
160
275
460
Between electrodes
kV
160
275
一
一
Break
kV
410
650/750
950+206
Rated lightning impulse withstand voltage
To ground
kV
350
550/650
1050
Between electrodes
kV
350
550/650
一
-
5-minute zero gauge pressure power frequency withstand voltage
5-minute zero gauge pressure power frequency withstand voltage
For inquiries about AC/DC power supply panel, uninterruptible power supply, circuit breaker or price list, please leave your email to us and we will be in touch within 24 hours.