As a professional and high-quality manufacturer of Ceramic pillar high-voltage AC circuit breakers, you can rest assured to purchase Ceramic pillar high-voltage AC circuit breakers from our factory. We will provide you with the best after-sales service and timely delivery.
Ceramic pillar high-voltage AC circuit breaker is equipped with CT20 spring operating mechanism, adopts self-arc extinguishing principle, and has single-break structure. The three poles of each circuit breaker are installed on a frame to realize three-phase mechanical linkage through transmission mechanism. The electric control can realize remote and local operation.
Main technical parameters of the product
Item No. LW36-72.5
1 Rated voltage kV72.5
2 Rated current A 1250 3150
3 Rated short-circuit breaking current kA 31.5
4 Rated short-time withstand current kA31.5 (4s)
5 Rated peak withstand current kA 80
6 Rated lightning impulse withstand voltage kV break 350+60 to ground 350
7 Rated 1 min power frequency withstand voltage kV break 160+42 to ground 160
8 Mechanism model CT20 spring operating mechanism
Ceramic pillar high-voltage AC circuit breaker product performance features
1Excellent breaking performance
2Long electrical life
3Reliable insulation performance
4Long mechanical life
5Safe and reliable operation, low maintenance workload
Ceramic pillar high-voltage AC circuit breaker main technical parameters
Rated voltage
NAME
NUITV
LW36-72.5
LW25-126/145
LW25-252
LW15B-252/LW15-252
66
126/145
252
252
Rated frequency
Hz
50
50
50
50
Rated current
A
125,031,504,000
20,003,150
4000
31,504,000
Rated breaking current
kA
25,31.5
40/31.5
40
50
Rated closing current
kA
80
100/80
100
125
Rated short-time withstand current and duration
kA
31.5(4s)
40(4s)/31.5(4s)
40(4s)
50(4s)
Rated peak withstand current
kA
80
100/80
100
125
Near-zone fault breaking current
kA
lex 90%le x75%
Rated out-of-step breaking current
kA
lex 25%
Creepage distance
cm/kV
3.1
2.5,3.1
Break
kV
160+42
315
395+145
Dry Test
To ground
kV
160
275
460
1 minute power frequency withstand voltage
Between electrodes
kV
160
275
一一
-
1 minute power frequency withstand voltage
Break
kV
160+42
275
395+145
Wet test
To ground
kV
160
275
460
Between electrodes
kV
160
275
一
一
Break
kV
410
650/750
950+206
Rated lightning impulse withstand voltage
To ground
kV
350
550/650
1050
Between electrodes
kV
350
550/650
一
-
5-minute zero gauge pressure power frequency withstand voltage
5-minute zero gauge pressure power frequency withstand voltage
kV
84
95/124
189
189
Closing time
Closing time
ms
<150
w150
50
w100
Opening time
Opening time
ms
w30
w30
w30
w25
Breaking time
Breaking time
ms
w60
w60
w60
w60
Closing and opening time
Closing and opening time
ms
40-60
40-60
50-70
40-60
Operation time difference
Operation time difference
Separation
ms
w2
w2
w2
w2
Inter-pole
Inter-pole
combination
ms
w4
Rated reclosing operation cycle
Rated reclosing operation cycle
0.3s--180s-O-0.3S-CO- 180s-CO
Gas rated pressure
Gas rated pressure
MPa
0.5;0.4
0.5
0.6
0.6
SF6 gas alarm/locking pressure
SF6 gas alarm/locking pressure
MPa
0.45/0.40,0.35/0.30
0.45/0.40
0.55/0.50
0.55/0.50
NUIT
LW36-72.5
LW25-126/145
LW25-252
LW15B-252/LW15-252
%
w0.5
1w0.5
w0.5
wO.5
个
1
1
1
1
次
3000
3000
3000
3000
N
790
1250
1500
1500
N
750
750
1000
1000
N
750
1000
1250
1250
M Q
W50
w45
w45
w42
Spring operating mechanism
Spring operating mechanism构
Spring mechanism or hydraulic机构
Hydraulic or pneumatic
kg
4
6
30
30
kg
1000
1400
3500
4000/4500
GB/T1984.IEC60056
Hot Tags: Ceramic Pillar High-Voltage AC Circuit Breaker, China, Manufacturer, Supplier, Factory, Fashion, Discount, Quotation, Easy-maintainable